Macromatic offers this cross-reference as a service to our customers to assist in the selection of replacement products. Every effort has been made to insure that these products are electrically and functionally equivalent to the Macromatic products except as noted. Macromatic cannot be responsible for errors of printing or corrections of data taken from published competitive data. It is the user's responsibility to insure the suitability of the substitution.
If you have any questions regarding these cross-references, or need to cross reference any product not listed, please contact Macromatic.
* If a part number is not found, select the "Series Name" from the right-hand drop down.
Or select competitor part series:

800.238.7474
Product Specifications
PMPU-FA8


Use socket: 70169-D
Image may not be exact product—for reference only.
Competitor: Symcom
- Competitor Part #: 201A
- Series: 201
- Macromatic Equivalent: PMPU-FA8
- Differences: The Symcom 201A unit does not have overvoltage protection; the Macromatic PMPU-FA8 product does; the Macromatic unit also has a manual reset option
- Family: 3-PHASE MONITOR RELAY
- Function: PHASE LOSS, PHASE REVERSAL, PHASE UNBALANCE, UNDERVOLTAGE & OVERVOLTAGE
- Line-Line Voltage: 190-500V AC
- Output: 10A SPDT
Description of function:
When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized after the Restart Delay is completed. Any one of five fault conditions will de-energize the relay after a delay. As standard, re-energization is automatic upon correction of the fault condition. Manual reset is available if an external momentary N.C. switch is connected to pins 6 and 7. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting (see right).
Application Information
- Load (Burden): Less than 40 VA
- Response Times:
Power Up/Restart After Fault: Fixed 2 Seconds Drop-out Due to:
Phase Loss & Reversal
Phase Unbalance
Undervoltage
Overvoltage
100ms Fixed
Fixed 4 Seconds
Fixed 4 Seconds
Fixed 4 Seconds - Minimum/Maximum Voltage: 156-550V, 50/60Hz. +5%
- Reset: As standard, the PMP Series relays are in the Automatic Reset mode. However, they can be set in the Manual Reset mode by connecting an external N.C. switch across terminals 6 and 7. Upon application of line voltage, the PMP Series will go into Manual Reset mode if it recognizes a closure across terminals 6 and 7. After a fault clears, the relay will not reset until the N.C. switch is opened.
- Output Contacts: 10A @ 277V AC / 7A @ 30V DC;
1HP @ 250V AC, 1/2HP @ 125V AC, C300 Pilot Duty - Life: Mechanical: 10,000,000 operations, Full Load: 100,000 operations
- Temperature: -28o to 65o C (-18o to 149o F)
- Approvals: