Competitive Cross Reference
Macromatic offers this cross-reference as a service to our customers to assist in the selection of replacement products. Every effort has been made to insure that these products are electrically and functionally equivalent to the Macromatic products except as noted. Macromatic cannot be responsible for errors of printing or corrections of data taken from published competitive data. It is the user's responsibility to insure the suitability of the substitution.
If you have any questions regarding these cross-references, or need to cross reference any product not listed, please contact Macromatic.
* If a part number is not found, select the "Series Name" from the right-hand drop down.
Or select competitor part series:

800.238.7474
Product Specifications
THL-8024U-41


Use socket: N/A
Image may not be exact product—for reference only.
Competitor: Infitec
- Competitor Part #: BMS1S
- Series: BMS
- Macromatic Equivalent: THL-8024U-41
- Differences: Infitec unit works on 12VDC only; the Macromatic equivalent works on 24-240VAC & 12-48VDC
- Family: TIME DELAY RELAY
- Function: ON DELAY
- Timing Range: 1-1,023 SEC
- Input Voltage: 24-240V AC & 12-48V DC
- Output: 1A NORMALLY OPEN (SOLID STATE)
Description of function:
Function Chart:

Application Information
- Voltage Tolerance: AC Operation: +10/-15% of nominal voltage, 50/60 Hz +5%. DC Operation: +10/-15% of nominal voltage.
- Load (Burden): Maximum of 1 VA for all voltages
- Setting Accuracy: Constant Voltage & Temperature w/i specifications: +2% of set time or +50ms, whichever is greater. For Variable Voltage & Temperature w/i specifications: +5% of set time or +50 ms, whichever is greater.
- Repeat Accuracy : Constant Voltage & Temperature w/i specifications: +5% of set time or +0.02 seconds, whichever is greater. For Variable Voltage & Temperature w/i specifications: +0.1% of set time or +0.02 seconds, whichever is greater.
- Reset Time: 50ms
- Output Contacts: Normally Open Solid State 1A Continuous, 10A Inrush @ 65o C, Pilot Duty
- Life: No predictable failure if used within operating parameters.
Leakage Current (OFF-State): <5 ma @ 240VAC
Minimum Load Current: 20ma
Effective Voltage Drop (ON-State): Maximum 3V @ 1A for all voltages
- Temperature: Operating: -40o to 65oC (-40o to 149oF)
- Approvals:
Dimensions
Inches (Millimeters)