VWKP Series
Plug-in
12-120V
240-480V
Features |
|
Enclosure Style | Plug-in case utilizing industry-standard 8 pin octal sockets |
Configuration/ Contact Rating |
|
Approvals | |
Technical Documentation |
Operation:
Voltage Band Relays provide protection to equipment that is required to operate within an upper & lower voltage limit. As long as the operating voltage remains within an OVER & UNDER voltage range, the internal relay stays energized. If the operating voltage falls outside this range, the relay will drop-out.
Adjust the over voltage setting (Umax) between the full range as shown on the product nameplate. Adjust the under voltage setting (Umin) between 75% and 95% of the over voltage setting. The relay energizes (and the LED is Red) when the monitored voltage is between the over and under voltage settings. The relay de-energizes (and the LED is Green) when the monitored voltage falls outside the over or under voltage settings for a period longer than the drop-out time delay (t), which is adjustable from 0.1-10 seconds. The relay re-energizes when the monitored voltage returns to a value between the over and under voltage settings for a period longer than the pick-up time delay, which is fixed at 0.5 seconds.
Macromatic's Voltage Monitor Relays Knowledge Base contains general and technical industry articles to help you learn more about Voltage Monitor Relays.
12-120V
240-480V